Installation, Operation and Maintenance Instructions Document 1187D
Installation,
Operation and
Maintenance
Instructions for
Endurance
EBP Series Modulating Combination Boiler
(natural or propane gas)
EDP Series Modulating Hydronic Boiler
(natural or propane gas)
EDN Series Modulating Boiler, non ferrous
(natural or propane gas)
WARNING
If the information in this manual is not
followed exactly, a re or explosion may
result causing property damage, personal
injury or loss of life.
Do not store or use gasoline or other
ammable vapors and liquids in the vicinity
of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not
use any phone in your building.
Immediately call your gas supplier from a
nearby phone. Follow the gas supplier's
instructions.
If you cannot reach your gas supplier, call
the re department.
Installation and service must be performed
by a qualied installer, service agency, or gas
supplier.
WARNING
FOR YOUR SAFETY: This product must be installed and serviced by a professional service
technician, qualied in hot water boiler installation and maintenance. Improper installation and/or
operation could create carbon monoxide gas in ue gases which could cause serious injury, property
damage, or death. Improper installation and/or operation will void the warranty. As an additional
measure of safety, Laars strongly recommends installation of suitable carbon monoxide detectors in
the vicinity of this appliance and in any adjacent occupied spaces.
AVERTISSEMENT
Assurez-vous de bien suivres les instructions
données dans cette notice pour réduire au
minimum le risque d’incendie ou d’explosion
ou pour éviter tout dommage matériel, toute
blessure ou la mort.
Ne pas entreposer ni utiliser d’essence ni
d’autres vapeurs ou liquides inammables dans
le voisinage de cet appareil ou de tout autre
appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
Ne pas tenter d’allumer d’appareils.
Ne touchez à aucun interrupteur. Ne pas vous
servir des téléphones dansle bâtiment où vous
vous trouvez.
Appelez immédiatement votre fournisseur de
gaz depuis un voisin. Suivez les instructions
du fournisseur.
Si vous ne pouvez rejoindre le fournisseur de
gaz, appelez le sservice des incendies.
L’installation et l’entretien doivent être assurés par
un installateur ou un service d’entretien qualié ou
par le fournisseur de gaz.
H2313500D
A subsidiary of BRADFORD WHITE Corporation
Seitenansicht 0
1 2 3 4 5 6 ... 39 40

Inhaltsverzeichnis

Seite 1 - Endurance

Installation, Operation and Maintenance Instructions Document 1187DInstallation,Operation andMaintenance Instructions forEnduranceEBP Series Modulat

Seite 2 - TABLE OF CONTENTS

Page 10 LAARS Heating Systems CompanyFigure 13. 3" Vent Parts.Dimensions shown in inches.

Seite 3 - General Information

EndurancePage 11per foot (21mm per meter). Be sure to take this into consideration when choosing the vent terminal location.For applications requiring

Seite 4 - Venting Options

Page 12 LAARS Heating Systems Company2400-435 tee(to separateventing fromcombustion air)4" air terminal(field-supplied)4" combustion air pi

Seite 5 - 2.1 Concentric Direct Vent

EndurancePage 133.2 Domestic Water Piping (EBP only)1. Connect tempering (mixing) valve 12 “Hot” port to hot water outlet from unit. This valve shou

Seite 6

Page 14 LAARS Heating Systems CompanyFigure 18. EBP Domestic Water Piping with Recirculating Loop. WARNINGFailure to install a hot water tempering (m

Seite 7

EndurancePage 15Figure 19. Hydronic Piping EDP/EBP with Zone Valves.Figure 20. Piping, Single EDP/EBP Boiler for Multiple Temperature Systems.Figure 2

Seite 8

Page 16 LAARS Heating Systems CompanyEDP/EDN boilers installed in radiant (in oor) systems and other low mass boilers should be provided with a buff

Seite 9 - Figure 11. Vent System Pitch

EndurancePage 178. Connect boiler feed water supply with shut off valve to inlet connection of automatic ll valve. Locate in boiler outlet piping.9.

Seite 10 - Dimensions shown in inches

Page 18 LAARS Heating Systems Company5. Remove front cover.6. Switch Gas Shutoff Switch to “OFF”.7. Wait ve (5) minutes to clear out any gas. If

Seite 11

EndurancePage 19Commande de gaz multifonctionsInterrupteur de soupape de détente des gaz6. Interrupteur de fermeture de la soupape de détente des gaz

Seite 12 - SECTION 3

Page 2 LAARS Heating Systems CompanyTABLE OF CONTENTSSECTION 1.General Information1.1 Introduction ...

Seite 13

Page 20 LAARS Heating Systems CompanySECTION 5.Electrical Connections5.1 Electrical ConnectionsAll electrical wiring must conform to local codes and

Seite 14 - Hydronic Heat Piping

EndurancePage 211231 12 23 3ENDURANCE FIELDWIRING BOXT'STAT (T)GROUND120 VAC LINEC1CIRCULATORT'STAT (T)CIRCULATOR120 VAC NEUT.REDWHT/REDGRN/

Seite 15

Page 22 LAARS Heating Systems Companycirculator (120 volt, 5 amp maximum) between the blue wire and the white wire (neutral) (see Figure 26).4. Mult

Seite 16

EndurancePage 23Figure 31. Control Logic Example.Figure 32. EDP/EDN Flow Schematic.6. Calculated Setpoint for Outdoor Reset (shown as “CSP” – when us

Seite 17 - 4.4 Anti-Freeze

Page 24 LAARS Heating Systems Company6.4 Setpoint MenuThe setpoint menu is accessed by pressing the enter button, and holding it for 3 seconds. Move

Seite 18 - TO TURN OFF GAS TO APPLIANCE

EndurancePage 256.4. These do not show on the control display, but it is helpful to know how they affect the control logic of the Endurance units.6.5.

Seite 19 - NOTICE D’UTILISATION

Page 26 LAARS Heating Systems Company6.6.2 Alarm AcknowledgeWhen an alarm is activated (LO or one of the F codes), the control will ash between the

Seite 20 - Electrical Connections

EndurancePage 276.6.8 Field-Supplied Outdoor Reset ControlsWhen a stand-alone outdoor reset control is used with the Endurance, it will only have the

Seite 21

Page 28 LAARS Heating Systems Companyet l’inclinaison horiztonale qui conviennent et s’assurer que le système est exempt d’obstruction, d’étranglemen

Seite 22 - Using the Boiler Control

EndurancePage 297. When there is a call for heat, the pump and the blower will start, the display will show the supply temperature. The appliance wil

Seite 23

EndurancePage 3SECTION 1.General Information1.1 IntroductionEBP - This appliance is a low pressure, direct vent, hot water boiler that provides prior

Seite 24 - 6.4 Setpoint Menu

Page 30 LAARS Heating Systems CompanyThe control displays the supply temperature, by default, and the user can access the heat exchanger inlet temper

Seite 25 - 6.6 Other Control Functions

EndurancePage 31Figure 35. Gas Valve.8.11 Thermostatic Union (EDP/EDN)The thermostatic union is a 1¼" NPTF union which must be mounted at the ow

Seite 26 - Button Action Result

Page 32 LAARS Heating Systems CompanyFigure 36. EDP/EDN Wiring Diagram.RRRESET SWITCHSUPPLYTHERMISTORBLRETURNTHERMISTORTANKTHERMISTORORGRFLOW SWITCHB

Seite 27 - Boiler Start Up

EndurancePage 337. 10 seconds after establishing combustion and proof of ame (via the ame rod signal to ground), the ignitor will be de-energized.8

Seite 28 - 7.3 Firing Burner

Page 34 LAARS Heating Systems Companyit is ashing three times, for ignition control lockout. If it is, then that is a combustion lockout.a. Poor Co

Seite 29 - Description

EndurancePage 35to go through a normal cycle. If during this cycle there is no ue odor, repair the leaky joints in the ue pipe.f. Safety limit trip

Seite 30 - Ignitor gets hot

Page 36 LAARS Heating Systems CompanyGas valve regulation problems can also cause delayed ignitions. See “Gas valve calibration”.Incorrect gas orice

Seite 31 - Servicing

EndurancePage 37Failure of the water ow switch to operate during a hot water draw prevents boiler water from owing through the DHW heat exchanger an

Seite 32 - TRANSFORMER

Page 38 LAARS Heating Systems CompanySECTION 12.Parts IdenticationItem # Description EBP0110 EBP0175 EDP0110 EDP0175 EDN0110 EDN01751. Pan,

Seite 33

EndurancePage 39Model EBP/EDP/EDN Control Panel3332254131410125See ControlPanel Drawing133176 112023921218Model EDP/EDN152930 31Model EBP/EDP/EDN Cont

Seite 34 - 2) or contamination

Page 4 LAARS Heating Systems CompanyOptions CodeX = NoneRevision2 = Second Revisionb. The Canadian Electrical Code (CSA C22.1), latest edition.c.

Seite 35 - Symptom Evaluations

H2313500DA subsidiary of BRADFORD WHITE Corporation20 Industrial Way, Rochester, NH 03867 • 603.335.6300 • Fax 603.335.33551355 Kuehner Drive, Simi Va

Seite 36 - 11.3 Noisy Operation

EndurancePage 5The following sections describe the requirements for each of these methods.IMPORTANT NOTE REGARDING ENDURANCE VENTING: Regardless of th

Seite 37 - 11.5 High Gas Consumption

Page 6 LAARS Heating Systems CompanyFigure 5. Horizontal Vent Kit 2400-009.Conguration 1:Maximum horizontal = 28"Maximum vertical = 26"(Me

Seite 38 - Parts Identication

EndurancePage 7Figure 7. Concentric Vent Parts.Dimensions shown in inches.

Seite 39

Page 8 LAARS Heating Systems CompanyFigure 8. Vent Terminal Clearance. U.S. Installations (see note 1) Canadian Installations (see note 2)A= Clea

Seite 40 - (Sales, Service)

EndurancePage 9The vertical vent terminal must be placed such that the bottom of the vent cap is at least 2-feet (0.6m) above any structure (such as t